500kW ON-GRID - Power Inverter Description

Input DC

 
  • Max. DC power 
  • Max. Input voltage
  • Trigger voltage
  • Max. Input current
  • MPPT voltage range
  • MPPT tracking ways
  • Number of DC Inputs
  • 550kW
    1000V
    480V
    1200A
    450-850V
    2
    10 (optional)

    Output AC

     
  • Rated power 
  • Rated grid voltage
  • Max. output current
  • Rated frid frequency
  • Grid voltage range
  • Grid frequency range
  • Output current THD (at rated power
  • Power factor at rated power
  • Output voltage DC component
  • AC output / Output terminal
  • 550kW
    270V
    1180A
    50Hz
    230-297V
    49.5-50.2Hz
    ≤2%
    ≥0.99
    <0.5%
    4xM10/Copper Bar

    System Data

     
  • Max. efficiency 
  • European efficiency
  • Degree of protection
  • Self-consumption at night
  • Operating temperature range
  • Storage temperature range
  • Cooling method
  • Relative humidity
  • Max. altitude
  • Fresh air consumption
  • Display
  • Standard communication
  • Optional communication
  • 98.7% (No transformer)
    98.4% (No transformer)
    IP21 (Indoor)
    ≤60W
    -20°C - +50°C
    -40°C - +80°C
    By fan
    ≤95%, non-condensing
    6000m
    5000m3/h
    LCD
    RS485
    Ethernet/GPRS

    Mechanical data

     
  • Dimensions (W x H x D)
  • Weight
  • 1735 x 1980 x 1080mm
    1400kg


    500kW ON-GRID - Power Inverter

    Application, Features and Benefits
    • Wide DC input voltage range.
    • Maximum efficiency is more than 98.7%, European efficiency reaches 98.4%.
    • Double lines MPPT function.
    • MPPT efficiency >99.9%.
    • LCD displays different language screen.
    • Perfect protection function.
    • Meets STate Grid LVRT requirements.
    • Remote parameter monitoring function.
    • Remote active power adjustable function (0-100%).
    • Adjustable reactive power, power factor range will head 0.9 or back 0.9.
    • Over temperature linear derating function.
    • Drive signal spdif out and avoid other signal interference.
    • LCL inverter filter and smaller harmonic.
    • Smar controlled cooling fan, automatically match high and low speed and save electricity to improve generation capacity.
    • Structure optimization design and small occupation space.
    • Automatically on and off model requires no manual intervention.
    • Heat dehumidification function.
    • Monitors all data of running machine.
    • Keeps fault and operation record, warning signal when fault.